| Technical Data |
: |
Rated Voltage Max : 300/500 V |
| Test Voltage |
: |
Core : core : 1000 V |
| |
|
Core : screen : 1000 V |
| Insulation resistance min |
: |
25M Ohm x km |
| Mutual capacitance |
: |
max. 250 pF/m |
| Capacitance between any core or screen |
: |
400 pF/m |
| Temperature rating |
: |
During operation : - 40°C up to + 70 °C |
| |
|
During installation : -0°C up to + 50 °C |
| Minimum bending radius |
: |
8 x overall diameter |
| Note |
: |
- Flame retardant according to BS 4066 part 3 |
| |
|
- Low Smoke Zero Halogen Flame Retardant Cables to IEC 754/IEC 61034 |
| |
|
are optional |
| Cable Construction |
: |
- Conductors of plain copper, sizes 1/0.8, 1/1.13, 16/0.2, 24.02* |
| |
|
or 7/0.53mm |
| |
|
- Insulation of PVC compound type TI1 according to BS 6746 |
| |
|
- Colour and number coded |
| |
|
- Cores twisted to pairs, pairs to cable (two pairs manufactured as quad) |
| |
|
- Binder of PETP tape (except one pair cables), minimum overlap of 25% |
| |
|
- Collective screen of aluminium/PETP tape, 0.0024mm thick, |
| |
|
over tinned drain wire 0.5mm2, minimum overlap of 25% |
| |
|
- Bedding of PVC compound type TM1 accroding to BS 6746, Black |
| |
|
- Armour of galvanized steel wires according to BS 1442 |
| |
|
- Sheath of PVC compound type TM1 according to BS 6746, Black |
| Application |
: |
It is used for transmission of analogous and digital signals in and around |
| |
|
process plants, dry and damp industries and recommended for underground |
| |
|
burial. |